Report ID: 1806SM2010 / Report | |
SUMMARY OF INSPECTOR COMMENTS | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
"This is not the entire report. The complete report may include additional information of concern to the client. It is recommended that the client read the complete report." The summary includes only items, which in the inspector's opinion meet the state's requirements. The inspector and HouseMaster are not responsible for the items which in the opinion of any interested part were either included in the summary, but should not be omitted; or should have been included in the summary, but were omitted. Please call our office at (864) 641-6180 with any concerns after review. Any questionable issues should be discussed with the Inspector and/or Inspection Company before closing.
NOTE #1: While listings in this Summary may serve as a guide to help prioritize remedial needs, the final decision regarding any action to be taken must be made by the client following consultation with the appropriate specialists and/or professional qualified contractors. HouseMaster recommends that a repair review/re-inspection be performed of any repairs to subject property after inspections to protect the client before closing. NOTE #2: Directions are normally as though facing structure from front at street. NOTE #3: Not all areas of concerns were photographed. Client should consider photos as a continuation, enhancement , and part of the original report. Client is advised to read the entire inspection report and any other reports performed/provided before closing. If there are any concerns with rot/decay/wood destroying insect damage of wood/elements, either on the exterior, interior or in the sub-structure, client is advised that all areas of wood were not probed, photographed, and reported. Client should infer that there are additional areas of rot/decay at other locations and the entire element should be evaluated by a qualified professional contractor. Any repairs made from this report should be considered a starting point and the entire element of concern should be evaluated/corrected by a qualified professional contractor for any possible concealed, hidden, or items not reported/mentioned within this inspection report. This should be the recommendations for any other item/element/component mentioned in this report. Thank you for using HouseMaster. |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
1. ROOFING
2. EXTERIOR ELEMENTS
4. GARAGE-CARPORT
6. INTERIOR ELEMENTS
7. KITCHEN ELEMENTS
9(A) . Master Bath
9(B) . Full Bath - Main Level Bedroom
9(C) . Full Bath - Main Level
9(D) . Full Bath - Second floor
9(E) . Full Bath Bonus Room
10. ELECTRIC SYSTEM
11. COOLING SYSTEM
12. HEATING SYSTEM
14. HOT WATER SUPPLY
15. FOUNDATION / SUB-STRUCTURE
16. FOUNDATION AREA WATER PENETRATION
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() |
Report ID: 1806SM2010 / Report |
INVOICE |
Advanced Property Inspections LLC DBA HouseMaster
3620 Pelham Road PMB # 263 Greenville SC 29615-5044 Office - 864-641-6180 SC License # RBI-48724 NC License #3614 |
Inspection Date: 6/7/2018
Inspected By: Stuart Malamut |
Customer Info: | Inspection Property: |
Sample Report Joel Lewis |
7 Main St Greenville SC 29615 |
|
||||
Tax $0.00 |
||||
Total Price $0.00 | ||||
Payment Method:
Payment Status:
Notes:
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() |
Report ID: 1806SM2010 / Report |
Prepared for Exclusive Use by: |
Sample Report Joel Lewis |
Address of Property: |
7 Main St Greenville SC 29615 |
Date of Service: |
6/7/2018 |
![]() |
Company Providing Service: |
Stuart Malamut SC License # RBI-48724 |
Advanced Property Inspections LLC DBA HouseMaster |
3620 Pelham Road PMB # 263 Greenville SC 29615-5044 Office - 864-641-6180 SC License # RBI-48724 NC License #3614 |
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() |
Report ID: 1806SM2010 / Report |
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
|
|||||
INSPECTION INFORMATION | ||||||||||||||||
|
|
INSPECTION DETAILS | |||||||||||
|
INTRODUCTION |
The purpose of this
report is to render the inspector's professional opinion of the
condition of the inspected elements of the referenced property
(dwelling or house) on the date of inspection. Such opinions are
rendered based on the findings of a standard limited time/scope
home inspection performed according to the Terms and Conditions of
the Inspection Order Agreement and in a manner consistent with
applicable home inspection industry standards. The inspection was
limited to the specified, readily visible and accessible installed
major structural, mechanical and electrical elements (systems and
components) of the house. The inspection does not represent a
technically exhaustive evaluation and does not include any
engineering, geological, design, environmental, biological,
health-related or code compliance evaluations of the house or
property. Furthermore, no representations are made with respect to
any concealed, latent or future conditions.
|
The GENERAL
INSPECTION LIMITATIONS on the following page provides information
regarding home inspections, including various limitations and
exclusions, as well as some specific information related to this
property. The information contained in this report was prepared
exclusively for the named Clients and is not transferable without
the expressed consent of the Company. The report, including all
Addenda, should be reviewed in its entirety.
|
REPORT TERMINOLOGY |
The following
terminology may be used to report conditions observed during the
inspection. Additional terms may also be used in the report:
|
SATISFACTORY
- Element was functional at the time of inspection. Element was
in working or operating order and its condition was at least
sufficient for its minimum required function, although routine
maintenance may be needed.
|
FAIR -
Element was functional at time of inspection but has a probability
of requiring repair, replacement or other remedial work at any time
due to its age, condition, lack of maintenance or other factors.
Have element regularly evaluated and anticipate the need to take
action.
|
POOR -
Element requires immediate repair, replacement, or other remedial
work, or requires evaluation and/or servicing by a qualified
specialist.
|
NOT APPLICABLE
- All or individual listed elements were not present, were not
observed, were outside the scope of the inspection, and/or were not
inspected due to other factors, stated or otherwise.
|
NOT INSPECTED
(NOT RATED) - Element was disconnected or de-energized, was not
readily visible or accessible, presented unusual or unsafe
conditions for inspection, was outside scope of the inspection,
and/or was not inspected due to other factors, stated or otherwise.
Independent inspection(s) may be required to evaluate element
conditions. If any condition limited accessibility or
otherwise impeded completion of aspects of the inspection,
including those listed under LIMITATIONS, it is recommended that
limiting factors be removed or eliminated and that an inspection of
these elements be arranged and completed prior to closing.
|
IMPORTANT
NOTE: All repair needs or recommendations for further evaluation
should be addressed prior to closing. It is the client’s
responsibility to perform a final inspection to determine the
conditions of the dwelling and property at the time of closing. If
any decision about the property or its purchase would be affected
by any condition or the cost of any required or discretionary
remedial work, further evaluation and/or contractor cost quotes
should be obtained prior to making any such
decisions.
|
NATURE OF THE FRANCHISE RELATIONSHIP |
The Inspection
Company ("Company") providing this inspection report is a
franchisee of HouseMaster LLC ("Franchisor"). As a franchisee,
the Company is an independently owned and operated business that
has a license to use the HouseMaster names, marks, and certain
methods. In retaining the Company to perform inspection services,
the Client acknowledges that Franchisor does not control this
Company’s day-to-day activities, is not involved in
performing inspections or other services provided by the Company,
and is in no way responsible for the Company’s actions.
Questions on any issues or concerns should be directed to the
listed Company.
|
GENERAL INSPECTION LIMITATIONS |
CONSTRUCTION
REGULATIONS - Building codes and construction standards vary
regionally. A standard home inspection does not include
evaluation of a property for compliance with building or health
codes, zoning regulations or other local codes or ordinances. No
assessments are made regarding acceptability or approval of any
element or component by any agency, or compliance with any specific
code or standard. Codes are revised on a periodic basis;
consequently, existing structures generally do not meet current
code standards, nor is such compliance usually required. Any
questions regarding code compliance should be addressed to the
appropriate local officials.
|
HOME MAINTENANCE
- All homes require regular and preventive maintenance to
maximize the economic life spans of elements and to minimize
unanticipated repair or replacement needs. Annual maintenance costs
may run 1 to 3% (or more) of the sales price of a house depending
on age, design, and/or the degree of prior maintenance. Every
homeowner should develop a preventive maintenance program and
budget for normal maintenance and unexpected repair expenses.
Remedial work should be performed by a specialist in the
appropriate field following local requirements and best
practices.
|
ENVIRONMENTAL
AND MOLD ISSUES (AND EXCLUSIONS) - The potential health effects
from exposure to many elements found in building materials or in
the air, soil, water in and/or around any house are varied. A home
inspection does not include the detection, identification or
analysis of any such element or related concerns such as, but not
limited to, mold, allergens, radon, formaldehyde, asbestos, lead,
electromagnetic fields, carbon monoxide, insecticides,
refrigerants, and fuel oils. Furthermore, no evaluations are
performed to determine the effectiveness of any system designed to
prevent or remove any elements (e.g., water filters or radon
mitigation). An environmental health specialist should be contacted
for evaluation of any potential health or environmental concerns.
Review additional information on MOLD/MICROBIAL ELEMENTS
below.
|
AESTHETIC
CONSIDERATIONS - A standard building inspection does not
include a determination of all potential concerns or conditions
that may be present or occur in the future including
aesthetic/cosmetic considerations or issues (appearances, surface
flaws, finishes, furnishings, odors, etc.).
|
DESIGN AND
ADEQUACY ISSUES - A standard home inspection does not
include any element design or adequacy evaluations including
seismic or high-wind concerns, soil bearing, energy efficiencies,
or energy conservation measures. It also does not address in any
way the function or suitability of floor plans or other design
features. Furthermore, no determinations are made regarding product
defects notices, safety recalls, or other similar manufacturer or
public/private agency warnings related to any material or element
that may be present in any house or on any property.
|
AGE ESTIMATIONS
AND DESIGN LIFE RANGES - Any age estimations represent the
inspector's opinion as to the approximate age of components.
Estimations may be based on numerous factors including, but not
limited to, appearance and owner comment. Design life ranges
represent the typical economic service life for elements of similar
design, quality and type, as measured from the time of original
construction or installation. Design life ranges do not take into
consideration abnormal, unknown, or discretionary factors, and are
not a prediction of future service life. Stated age or
design life ranges are given in "years," unless otherwise noted,
and are provided for general guidance purposes only. Obtain
independent verification if knowledge of the specific age or future
life of any element is desired or required.
|
ELEMENT
DESCRIPTIONS - Any descriptions or representations of element
material, type, design, size, dimensions, etc., are based primarily
on visual observation of inspected or representative components.
Owner comment, element labeling, listing data, and rudimentary
measurements may also be considered in an effort to describe an
element. However, there is no guarantee of the accuracy of any
material or product descriptions listed in this report; other or
additional materials may be present. Independent evaluations and/or
testing should be arranged if verification of any element's makeup,
design, or dimension is needed. Any questions arising from the use
of any particular terminology or nomenclature in this report
should be addressed prior to closing.
|
REMEDIAL WORK
- Quotes should be obtained prior to closing from qualified
(knowledgeable and licensed as required) specialists/contractors to
determine actual repair/replacement costs for any element or
condition requiring attention. Any cost estimates provided with a
home inspection, whether oral or written, only represent an
approximation of possible costs. Cost estimates do not reflect all
possible remedial needs or costs for the property; latent concerns
or consequential damage may exist. If the need for remedial work
develops or is uncovered after the inspection, prior to performing
any repairs contact the Inspection Company to arrange a
re-inspection to assess conditions Aside from basic maintenance
suitable for the average homeowner, all repairs or other remedial
work should be performed by a specialist in the appropriate field
following local requirements and best practices.
|
SELLER
DISCLOSURE - This report is not a substitute for Seller
Disclosure. A Property History Questionnaire form may be
provided with this report to help obtain background information on
the property in the event a full Seller Disclosure form is not
available. The buyer should review this form and/or the Seller
Disclosure with the owner prior to closing for clarification or
resolution of any questionable items. A final buyer inspection of
the house (prior to or at the time of closing) is also
recommended.
|
WOOD-DESTROYING
INSECTS/ORGANISMS - In areas subject to wood-destroying insect
activity, it is advisable to obtain a current wood-destroying
insect and organism report on the property from a qualified
specialist, whether or not it is required by a lender. A standard
home inspection does not include evaluation of the nature or
status of any insect infestation, treatment, or hidden damage, nor
does it cover issues related to other house pests or nuisances or
subsequent damage.
|
ELEMENTS NOT
INSPECTED - Any element or component not evaluated as part of
this inspection should be inspected prior to closing. Either make
arrangements with the appropriate tradesman or contact the
Inspection Company to arrange an inspection when all elements are
ready for inspection.
|
HOUSE
ORIENTATION - Location descriptions/references are provided for
general guidance only and represent orientations based on a view
facing the front of the house from the outside. Any references
using compass bearings are only approximations. If there are any
questions, obtain clarification prior to closing.
|
CONDOMINIUMS
- The Inspection of condominium/cooperative do not include
exteriors/ typical common elements, unless otherwise noted. Contact
the association/management for information on common element
conditions, deeds, and maintenance responsibilities.
|
MOLD AND MICROBIAL ELEMENTS / EXCLUSIONS |
The purpose and
scope of a standard home inspection does not include the
detection, identification or assessment of fungi and other
biological contaminants, such as molds, mildew, wood-destroying
fungi (decay), bacteria, viruses, pollens, animal dander, pet or
vermin excretions, dust mites and other insects. These elements
contain/carry microbial particles that can be allergenic,
infectious or toxic to humans, especially individuals with asthma
and other respiratory conditions or sensitivity to chemical or
biological contaminants. Wood-destroying fungi, some molds, and
other contaminants can also cause property damage. One particular
biological contamination concern is mold. Molds are present
everywhere. Any type of water leakage, moisture condition or
moisture-related damage that exists over a period of time can lead
to the growth of potentially harmful mold(s). The longer the
condition(s) exists, the greater the probability of mold growth.
There are many different types of molds; most molds do not create a
health hazard, but others are toxic.
|
Indoor mold
represents the greatest concern as it can affect air quality and
the health of individuals exposed to it. Mold can be found in
almost all homes. Factors such as the type of construction
materials and methods, occupant lifestyles, and the amount of
attention given to house maintenance also contribute to the
potential for molds. Indoor mold contamination begins when spores
produced by mold spread by air movement or other means to an area
conducive to mold growth. Mold spores can be found in the air,
carpeting, insulation, walls and ceilings of all buildings. But
mold spores only develop into an active mold growth when exposed to
moisture. The sources of moisture in a house are numerous and
include water leakage or seepage from plumbing fixtures,
appliances, roof openings, construction defects (e.g., EIFS wall
coverings or missing flashing) and natural catastrophes like floods
or hurricanes. Excessive humidity or condensation caused by faulty
fuel-burning equipment, improper venting systems, and/or inadequate
ventilation provisions are other sources of indoor moisture. By
controlling leakage, humidity and indoor air quality, the potential
for mold contamination can be reduced. To prevent the spread of
mold, immediate remediation of any water leakage or moisture
problems is critical. For information on mold testing or
assessments, contact a qualified mold specialist.
|
Neither the
evaluation of the presence or potential for mold growth, nor the
identification of specific molds and their effects, fall within the
scope of a standard home inspection. Accordingly, the Inspection
Company assumes no responsibility or liability related to the
discovery or presence of any molds, their removal, or the
consequences whether property or health-related.
|
ADDITIONAL COMMENTS |
The licensee certifies that this inspection was conducted pursuant to the SC Home Inspection Standards of Practice & applicable home inspection industry standards. Furthermore, neither the licensee nor inspection company has any interest, present or contemplated, in this property and neither the retention of the inspection company or compensation paid is contingent on report findings. Due to seasonal factors or weather conditions, evaluation of some elements may have been severely restricted or not possible. Client should assess the level of concern that may exist due to such restrictions and arrange additional inspections when conditions permit or otherwise address prior to closing. If there are any questions on the need for further inspections or other work, contact the local HouseMaster office. |
(c) Copyright 2001 - 2025 HouseMaster
|
Each HouseMaster
Franchise is an Independently Owned and Operated Business.
|
![]() |
![]() Report ID: 1806SM2010 / Report |
DESCRIPTION: Moderate Slope |
MATERIAL: Shingle |
ESTIMATED AGE: 10 to 15 years |
DESIGN LIFE: 20 to 25 years |
LOCATION: Whole House |
INSPECTION METHOD: Ladder at Eaves From adjacent window |
SKYLIGHT(S): Four |
CHIMNEY/VENT: Brick |
SPECIAL LIMITATIONS: Inaccessible areas of Roof due to height/location. Various attic areas inaccessible for inspection |
S | F | P | NA | NI | ||
![]() |
1.0 | ROOFING-MAIN (1) Note: The evaluation of a roof is primarily a visual assessment based on general roofing appearances and not all areas of
roofing possibly could not be seen due to height and slope of roof. The verification of actual roofing materials, installation
methods or roof age is generally not possible. If roofing system was recently installed, client should attempt to obtain
from the seller any information regarding manufacturers warranties and/or guarantees prior to closing. Conditions such as
hail damage or the lack of underlayment may not be readily detectible and may result in latent concerns. If the inspection
was restricted to viewing from the ground and/or was affected by weather conditions or other limitations, a roofer's
assessment would be advisable, particularly if the roofing is old or age is unknown and due to the standard home
inspection limitations.
(2) Note : Areas of scuffed shingles with granule loss observed at rear areas, client may wish to have further evaluation by a
qualified roofing contractor .
Note : Pictures shown are examples only , not all areas of concern have pictures . |
||||
![]() |
1.1 | CHIMNEYS / VENTS Note: Chimney and vent evaluations are based on external conditions only. Internal conditions, design, and venting
adequacy were not evaluated unless specifically indicated. A periodic check of all chimneys/vents is advisable as a
precautionary measure. A chimney sweep/contractor is often qualified to assess/maintain chimney/vent interiors. In some
cases the top may be inaccessible due to height-no interior evaluation performed. Have cleaned/checked as desired.
|
||||
![]() |
1.2 | EXPOSED FLASHING (s) | ||||
![]() |
1.3 | VENTILATION COVERS | ||||
![]() |
1.4 | PLUMBING STACKS Note: The flashing/boot seal at plumbing vents are prone to leakage. All vent pipe flashings should be checked
periodically as these will split/crack/deteriorate over time. These normally last approximately 7 to 12 years and owner
should monitor in the future to help prevent future leakage at vent pipe boots and should be repaired and/or sealed as
needed.
|
||||
![]() |
1.5 | RAIN GUTTERS / EAVETROUGHS Note: Recommend keeping gutter system clear of leaves and debris to allow proper water run off away from structure to
prevent water ponding near foundation. General maintenance and caulking/sealing of joints is required to maintain
prevention of gutter leakage. All gutters should be checked for damage, blockage, leakage or overflow on a regular basis
(at least twice annually). This is a limitation for a standard home inspection.
|
||||
![]() |
1.6 | DOWNSPOUTS / ROOF DRAINS Note: If not present/installed at time of inspection it is recommended to extend downspouts to move roof run-off water
away from the foundation a minimum 5 feet to prevent water penetration at foundation walls. Clean out gutter systems on
a regular basis to prevent possible rainwater intrusion at foundation walls. It is also recommended that any downspout
connected to an underground system be kept clean and free of blockage to allow the gutter system to function as
intended. If downspouts are already extended away from foundation walls and have buried drain lines, keeping these lines
clear is recommended so the entire gutter system functions as intended. Discuss with owner the termination points of
drains prior to closing so these can be checked for blockage periodically.
|
||||
![]() |
1.7 | FASCIA / SOFFITS | ||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
![]() 1.0(2) ROOFING-MAIN Item 1(Picture)
|
![]() 1.0(2) ROOFING-MAIN Item 2(Picture)
|
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
SIDING: Brick/Veneer |
SPECIAL LIMITATIONS: Vegetation |
S | F | P | NA | NI | ||
![]() |
2.0 | SIDING- BRICK (1) In need of Evaluation / Correction :
1.A lintel is a piece of steel that spans an opening (e.g., a door or window) and supports the masonry above it. Over time as steel lintels age, they rust and swell and deflect (i.e., become wavy) and create growing pressure within the masonry wall. This process is known as rust-jacking and if left unchecked can crack apart mortar and heave bricks out of alignment. The right and center area of the Garage opening has cracking above the lintel. Recommend evaluation/correction by qualified contractor. 2.Cracking at brick veneer at right side area . This condition is conducive to possible foundation concerns, foundation failure and/or soil movement. Due to concerns observed: Evaluation/correction by qualified professional foundation specialist and/or licensed professional engineer to determine the cause and significance of the cracks and necessary repairs. (2) Note: Limitation for inspection due to vegetation/shrubbery at various areas around home perimeter, conditions limits
inspection of elements for home inspection and wood destroying insect inspections. Client is advised to review these
areas during final walk thru prior to closing to ensure all concerns have been reviewed and/or inspected.
|
||||
![]() |
2.1 | WINDOWS Refer to INTERIOR ELEMENTS WINDOWS
|
||||
![]() |
2.2 | ENTRY DOORS In Need of Repair : Rot/decay at door threshold area at rear exterior door off family room. This condition is conducive to rot/decay at sub-structure. Conditions behind walls / subfloor are indeterminate as there could be further hidden damage. |
||||
![]() |
2.3 | STAIRS / STOOPS | ||||
![]() |
2.4 | RAILINGS | ||||
![]() |
2.5 | EXTERIOR ELEMENT LIMITATIONS Note: There is a potential that exterior and/or interior surfaces are covered with a lead-based paint, particularly in pre-1978 homes. If paint is intact or covered with another product the likelihood of the release of any significant lead is
minimized. No lead-based paint assessment is made as part of a standard home inspection. Individual concerns should be
considered and testing by a qualified specialist can be arranged if needed.
|
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
![]() 2.0(1) SIDING- BRICK Item 1(Picture)
| |
![]() 2.0(1) SIDING- BRICK Item 2(Picture)
| |
![]() 2.0(1) SIDING- BRICK Item 3(Picture)
|
![]() 2.2 ENTRY DOORS Item 1(Picture)
|
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
PATIO(S): Concrete |
PATIO LOCATION: Rear |
WALKWAY: Concrete |
DRIVEWAY: Concrete |
SPECIAL LIMITATIONS: Vegetation |
S | F | P | NA | NI | ||
![]() |
3.0 | WALKWAYS Note: All walkway surfaces should be constructed and maintained so that they slope away from the foundation and water runs off freely. Monitor after rainfalls for any pooling and correct as needed. |
||||
![]() |
3.1 | DRIVEWAY | ||||
![]() |
3.2 | SITE GRADING | ||||
![]() |
3.3 | PATIO Note: All patio surfaces should be maintained so that they slope away from the foundation and water runs off freely. Caulk/seal any cracking to prevent future expansion. |
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
DESCRIPTION: Multiple Car |
ROOF DESCRIPTION: Refer to ROOFING Section |
ROOF MATERIAL: Refer to ROOFING Section |
SPECIAL LIMITATIONS: Inaccessible areas Storage/Belongings |
S | F | P | NA | NI | ||
![]() |
4.0 | EXPOSED FRAMING | ||||
![]() |
4.1 | FLOOR SLAB Note: Minor cracks were found in the concrete floor. However they don't appear to be a structural concern and no trip
hazards were found. No immediate action is required, but the client(s) may wish to have repairs made or cracks sealed to
prevent further deterioration.
|
||||
![]() |
4.2 | WALLS / CEILINGS Note: Due to storage/personnel belongings at Garage walls, conditions limits inspection of elements for home inspection
and wood destroying insect inspections. Client is advised to review these areas during final walk thru prior to closing to
ensure all concerns have been reviewed and/or inspected.
|
||||
![]() |
4.3 | VEHICLE DOOR(S) In Need of Repair :
Prior/current possible termite damage observed at right side area of door frame opening , no visible tubes or termites were observed at time of inspection , repair as required , recommend further evaluation by a licensed pest control contractor . |
||||
![]() |
4.4 | DOOR OPERATOR(S) In Need of Repair: The garage door opener did not automatically reverse under reasonable resistance to closing. There is
a serious risk of injury, particularly to children, under this condition. Improvement may be as simple as adjusting the
sensitivity control on the opener; although some older models may not have this feature.
|
||||
![]() |
4.5 | GARAGE/CARPORT LIMITATIONS Due to storage/personnel belongings at Garage walls, conditions limits inspection of elements for home inspection and
wood destroying insect inspections. The garage walls were not fully visible, nor was the full slab. Client is advised to
review these areas during final walk thru prior to closing to ensure all concerns have been reviewed and/or inspected.
|
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
![]() 4.3 VEHICLE DOOR(S) Item 1(Picture)
|
![]() 4.3 VEHICLE DOOR(S) Item 2(Picture)
|
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
DESCRIPTION: Scuttle Walk-Up/In |
INSPECTION METHOD: Entered Limited Entry |
FRAMING: Wood Frame - Rafters |
SHEATHING: Structural panels |
INSULATION: Loose Fill |
SPECIAL LIMITATIONS: Height/No Walkway Insulation Inaccessible areas Insulation |
TOOLS USED FOR ATTIC INSPECTION: Flashlight Camera Outlet Tester |
S | F | P | NA | NI | ||
![]() |
5.0 | ROOF FRAMING Note: Attic was viewed from limited entry only due to design, insulation and/or excessive storage. Not all areas are
visible from entry. No concerns observed with visible framing. Further inspection would require entry and walking on joist
/ truss system that is covered in insulation which may cause cosmetic damage to ceilings below. This is beyond the
standard home inspection.
|
||||
![]() |
5.1 | ROOF DECK / SHEATHING Note: Attic was viewed from limited entry only due to design, insulation and/or excessive storage. Not all areas are
visible from entry. No concerns observed with visible sheathing. Further inspection would require entry and walking
on joist / truss system that is covered in insulation which may cause cosmetic damage to ceilings below. This is beyond
the standard home inspection..
|
||||
![]() |
5.2 | VENTILATION PROVISIONS | ||||
![]() |
5.3 | INSULATION | ||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
PREDOMINANT CEILINGS: Wood Frame |
PREDOMINANT WALLS: Wood Frame |
PREDOMINANT FLOORS: Wood Frame |
PREDOMINANT WINDOWS: Double Hung |
DETECTOR(S): Battery/Hard Wired |
DETECTOR LOCATION(S): Hall area (s) |
SLAB CONSTRUCTION: Not Applicable |
FIREPLACE(S): Type: Fireplace w/Gas Burner |
SPECIAL LIMITATIONS: Appliances Furnishing/Storage Finish materials |
S | F | P | NA | NI | ||
![]() |
6.0 | CEILINGS | ||||
![]() |
6.1 | WALLS Note: Typical drywall flaws such as picture holes, scrapes and holes were observed at various locations are not part of
the home inspection. This condition is mainly cosmetic in nature and should be repaired as desired.
|
||||
![]() |
6.2 | FLOORS | ||||
![]() |
6.3 | STAIRS | ||||
![]() |
6.4 | WINDOWS Note: Could not locate tempered glass stamp on windows in rear dining area and bonus room .. Generally tempered
glass is recommended at all windows in close proximity to floor for safety. Client should inquire about local practices for
safety concerns as not all jurisdictions may require this.
|
||||
![]() |
6.5 | RAILINGS | ||||
![]() |
6.6 | ROOM DOORS | ||||
![]() |
6.7 | DETECTOR TEST In Need of Repair: Missing detector at second floor hallway , replace for safety .
|
||||
![]() |
6.8 | FIREPLACE(S) Note: Fireplace
The NFPA (National Fire Protection Association) highly recommends an annual inspection of all chimneys, fireplaces, solid fuel-burning appliances, and vents by a qualified fireplace sweep/contractor. They also recommend an NFPA 211 Standard, Level II inspection upon sale or transfer of the property. A Level II inspection includes, not only cleaning the interior of the chimney pipe, but also the use of specialized tools and testing procedures such as video cameras, etc. to thoroughly evaluate the serviceability of the entire flue lining and fireplace/chimney system. If one has not been performed over the past 12 months, such an inspection is recommended before home changes ownership---for fire safety reasons |
||||
![]() |
6.9 | FIREPLACE GAS BURNERS Note: Gas logs/burners not evaluated due to pilot light not on for inspection. Recommend having pilot light on for final walk
thru for inspection/proper operation.
|
||||
![]() |
6.10 | GENERAL CONDITIONS Note: The residence is furnished, and in accordance with industry standards we only inspect those surfaces that are
exposed and readily accessible. We do not move furniture, lift carpets or rugs, nor do we remove or rearrange items
within closets or cabinets. On your final walk through, or at some point after furniture and personal belongings have been
removed, it is important that you inspect the interior portions of the residence that were concealed or otherwise
inaccessible and contact us immediately if any adverse conditions are observed that were not reported on in your
inspection report.Only viewable sections are part of this report
|
||||
![]() |
6.11 | INTERIOR ELEMENTS LIMITATIONS Floor tile , ceiling tile and other finished surfaces, particularly textured ceiling surfaces in pre- 1980 homes may possibly
contain asbestos. If the surface has been painted or coated and is undamaged, potential concerns related to exposure to
airborne asbestos are reduced ; however , if the ceiling is or becomes damaged, remedial measures will be required.
Bulk and / or air sampling by an asbestos specialist will be required to determine if the materials contain asbestos or if
there is an asbestos concern. Independent testing can be arranged if needed. In addition lead based paint was allowed
until 1978 , this is usually not a concern as long as the surface is intact and not damaged, independent testing can be
arranged if needed to confirm the presence of lead based paint, if the surface is damaged , then remedial measures will
be required ,
|
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
![]() 6.4 WINDOWS Item 1(Picture)
|
![]() 6.4 WINDOWS Item 2(Picture)
|
![]() 6.7 DETECTOR TEST Item 1(Picture)
|
Recommend inspection by an engineer or qualified contractor to determine the nature of the condition and whether remedial work is required to provide
level surfaces or to correct deficiencies.
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
LOCATION: Rear |
VENTILATOR: Down-Flow |
FREESTANDING RANGE/OVEN: Not Applicable |
DISHWASHER: Estimated Age: 0 to 5 years |
DISPOSAL: Estimated Age: 5 to 10 years |
COUNTERTOP RANGE: Estimated Age: Over 10 years Fuel: Gas |
WALL OVEN: Estimated Age: Over 10 years Electric |
SPECIAL LIMITATIONS: Appliances Storage/Obstructions |
S | F | P | NA | NI | ||
![]() |
7.0 | PLUMBING / SINK Note: Faucets/spout/drainage were functioning as intended and no observed leakage was present at time of inspection.
There were personal belongings in the cabinet and minor leakage can occur from removal of belongings and
bumping/damage of plumbing lines. It is recommended that clients inspect/review all plumbing connections at final walk
through prior to closing. Monitor in the future.
|
||||
![]() |
7.1 | COOKING UNIT/WALL OVEN(S)/COOK TOP Note: Cooking adequacies, anti-tip features, self-cleaning cycles, timers/clocks and electronics and other accessories are
not evaluated as part of a home inspection. Functional at time of inspection, anticipate repairs/servicing.
|
||||
![]() |
7.2 | DISHWASHER In Need of Repair: Dishwasher missing discharge loop. Condition is conducive to disposal waste contaminating
dishwasher.
|
||||
![]() |
7.3 | DISPOSAL Note: Disposal was operated without food and functioned as intended but no assessment could be made on food grinding
ability/capacity which is a limitation to the inspection. Do run your garbage disposal regularly. Frequent use prevents rust
and corrosion, assures that all parts stay moving and prevents obstructions from accumulating.
|
||||
![]() |
7.4 | VENTILATOR Note: Due to the presence of cooking and washing equipment that can generate excess moisture, and in the case of gas cooking appliances which can discharge possible contaminants into the air, adequate kitchen area venting is required (window and/or mechanical vent). Recommend maintaining/cleaning the filter and exhaust duct, if present, for proper function in the future. If not already present, exhaust air ventilators that discharge directly to the exterior should be considered. |
||||
![]() |
7.5 | CABINETRY/COUNTERTOP Note: Inspection of countertops/cabinetry is limited to a check of visible counter areas and a representative number of
cabinet components.
|
||||
![]() |
7.6 | REFRIGERATOR Note: Refrigerators and ice makers are not within the scope of a South Carolina Home Inspection and are not inspected
nor are the water/ice maker lines inspected. If there is a refrigerator installed in the home at the time of inspection we do
not move the refrigerator to inspect behind it. By moving the refrigerator it may cause damage to the floor, ice maker line
and/or the refrigerator itself. If you wish to know its overall condition you should consult a qualified appliance person for
review prior to closing.
|
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
![]() 7.2 DISHWASHER Item 1(Picture)
|
![]() 7.2 DISHWASHER Item 2(Picture)
|
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
Special Limitations: Appliances Storage/Obstructions |
S | F | P | NA | NI | ||
![]() |
8.0 | DRYER VENT | ||||
![]() |
8.1 | LAUNDRY HOOK UP | ||||
![]() |
8.2 | ELECTRIC | ||||
![]() |
8.3 | LAUNDRY ELEMENTS LIMITATIONS Note: The washer connections are not tested at the time of inspection. The inspector visually looks at the connections and
the wall around the area (when accessible or not blocked by the height of some washers) There were no signs of stains
or leaks noted at the time of inspection unless noted below with comments/concerns.
|
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
DESCRIPTION: Full bath w/stall |
LOCATION: Master Bedroom |
VENTILATOR(S): Combo Fan/Light |
S | F | P | NA | NI | ||
![]() |
9.0.A | VENTILATION Note: It is recommended to utilize the exhaust fan/open window when showering to allow for removal of excess humidity
to prevent future fungal growth to walls and ceilings. Ventilation exhaust fan was functioning as intended at time of
inspection. It is recommended cleaning these units a couple times a year to prevent dirt/lint from affecting the proper
performance of ventilation fans.
|
||||
![]() |
9.1.A | SINK(S) Note:
1. Faucets/spout/drainage were functioning as intended and no observed leakage was present at time of inspection. There were personal belongings in the cabinet and minor leakage can occur from removal of belongings and bumping/damage of plumbing lines. It is recommended that clients inspect/review all plumbing connections at final walk through prior to closing. Monitor in the future. 2. The shut off valves under sinks are not tested. By turning the valves it may cause them to leak also causing damage to the property. Shut off valves are not turned, tested, or operated. |
||||
![]() |
9.2.A | TOILET Note:
1. Toilet was functioning as intended and no observed leakage was present at time of inspection. Additionally, there were no cracks observed and toilet was properly secured to flooring. Monitor in the future. 2. The water supply valve was not tested. By turning the valve it may cause them to leak also causing damage to the property. Shut off valves are not turned, tested, or operated. |
||||
![]() |
9.3.A | BATHTUB Note:
1. Tub Faucets/spouts was observed at time of inspection Tub elements were functioning as intended. Monitor in the future. 2. Tub overflows are not tested at the time of inspection. Inspectors are unable to determine if the overflow is connected properly in the wall at the time of inspection. If the overflow line is not connected properly testing them can cause damage to the property. |
||||
![]() |
9.4.A | STALL SHOWER In Need of Repair: Hot/Cold is reversed which is a safety concern due to scalding potential. Repair as required.
|
||||
![]() |
9.5.A | BATHROOM LIMITATIONS Note: Only the viewable parts of the vent can be seen during a home inspection. Vent lines can be chased inside of walls
and buried below insulation in the attic. These areas are not viewable during a home inspection.
|
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
![]() 9.4.A STALL SHOWER Item 1(Picture)
|
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
DESCRIPTION: Full Bath |
LOCATION: Main Level Bedroom |
VENTILATOR(S): Combo Fan/Light |
S | F | P | NA | NI | ||
![]() |
9.0.B | VENTILATION Note: It is recommended to utilize the exhaust fan/open window when showering to allow for removal of excess humidity
to prevent future fungal growth to walls and ceilings. Ventilation exhaust fan was functioning as intended at time of
inspection. It is recommended cleaning these units a couple times a year to prevent dirt/lint from affecting the proper
performance of ventilation fans.
|
||||
![]() |
9.1.B | SINK(S) In Need of Repair :
Drain stopper is not functioning as intended as it does not release fully to allow the water to drain in a timely manner , repair as required . |
||||
![]() |
9.2.B | TOILET In Need of Repair: The toilet is loose at the floor and needs to be secured properly to prevent movement and/or possible
leakage which will damage sub flooring under toilet. Conditions under toilet at subfloor are indeterminate . Repair as
required.
Note: A new wax ring should be installed under all loose toilets. As the toilet loosens the seal that is formed from the toilet loosens and the seal is not as tight as it once was. This may result is a leak allowing waste water or sewage gases into the home from a deformed wax ring. |
||||
![]() |
9.3.B | BATHTUB In Need of Repair: Loose spout at wall surround and not sealed. Condition is conducive to water intrusion into wall cavity.
Recommend repair/caulking as needed.
|
||||
![]() |
9.4.B | BATHROOM LIMITATIONS Note: Only the viewable parts of the vent can be seen during a home inspection. Vent lines can be chased inside of walls
and buried below insulation in the attic. These areas are not viewable during a home inspection.
|
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
![]() 9.1.B SINK(S) Item 1(Picture)
|
![]() 9.3.B BATHTUB Item 1(Picture)
|
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
DESCRIPTION: Full bath w/stall |
LOCATION: Main Level Hallway |
VENTILATOR(S): Exhaust Fan |
S | F | P | NA | NI | ||
![]() |
9.0.C | VENTILATION Note: It is recommended to utilize the exhaust fan/open window when showering to allow for removal of excess humidity
to prevent future fungal growth to walls and ceilings. Ventilation exhaust fan was functioning as intended at time of
inspection. It is recommended cleaning these units a couple times a year to prevent dirt/lint from affecting the proper
performance of ventilation fans.
|
||||
![]() |
9.1.C | SINK(S) | ||||
![]() |
9.2.C | TOILET In Need of Repair: The toilet is loose at the floor and needs to be secured properly to prevent movement and/or possible
leakage which will damage sub flooring under toilet. Conditions under toilet at subfloor are indeterminate . Repair as
required.
Note: A new wax ring should be installed under all loose toilets. As the toilet loosens the seal that is formed from the toilet loosens and the seal is not as tight as it once was. This may result is a leak allowing waste water or sewage gases into the home from a deformed wax ring. |
||||
![]() |
9.3.C | BATHTUB | ||||
![]() |
9.4.C | STALL SHOWER In Need of Repair :
Faucet assembly is loose and subject to leaking , repair as required . |
||||
![]() |
9.5.C | BATHROOM LIMITATIONS Note: Only the viewable parts of the vent can be seen during a home inspection. Vent lines can be chased inside of walls
and buried below insulation in the attic. These areas are not viewable during a home inspection.
|
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
![]() 9.4.C STALL SHOWER Item 1(Picture)
|
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
DESCRIPTION: Full Bath |
LOCATION: Second floor Hallway |
VENTILATOR(S): Exhaust Fan |
SPECIAL LIMITATIONS: Under Bathroom Not Accessible |
S | F | P | NA | NI | ||
![]() |
9.0.D | VENTILATION Note: It is recommended to utilize the exhaust fan/open window when showering to allow for removal of excess humidity
to prevent future fungal growth to walls and ceilings. Ventilation exhaust fan was functioning as intended at time of
inspection. It is recommended cleaning these units a couple times a year to prevent dirt/lint from affecting the proper
performance of ventilation fans.
|
||||
![]() |
9.1.D | SINK(S) Note:
1. Faucets/spout/drainage were functioning as intended and no observed leakage was present at time of inspection. Monitor in the future. 2. The shut off valves under sinks are not tested. By turning the valves it may cause them to leak also causing damage to the property. Shut off valves are not turned, tested, or operated. |
||||
![]() |
9.2.D | TOILET Note:
1. Toilet was functioning as intended and no observed leakage was present at time of inspection. Additionally, there were no cracks observed and toilet was properly secured to flooring. Monitor in the future. 2. The water supply valve was not tested. By turning the valve it may cause them to leak also causing damage to the property. Shut off valves are not turned, tested, or operated. |
||||
![]() |
9.3.D | BATHTUB In Need of Repair :
1.When shower was engaged , water continued to drip/flow out of tub spout , this is usually a faulty diverter valve , repair as required . 2. Loose shower head at wall. Condition is conducive to leakage at water piping at interior wall cavity. |
||||
![]() |
9.4.D | BATHROOM LIMITATIONS Note: Only the viewable parts of the vent can be seen during a home inspection. Vent lines can be chased inside of walls
and buried below insulation in the attic. These areas are not viewable during a home inspection.
|
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
![]() 9.3.D BATHTUB Item 1(Picture)
|
![]() 9.3.D BATHTUB Item 2(Picture)
|
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
DESCRIPTION: Full bath w/stall |
LOCATION: Bonus Room |
VENTILATOR(S): Combo Fan/Light |
SPECIAL LIMITATIONS: Under Bathroom Not Accessible |
S | F | P | NA | NI | ||
![]() |
9.0.E | VENTILATION Note: It is recommended to utilize the exhaust fan/open window when showering to allow for removal of excess humidity
to prevent future fungal growth to walls and ceilings. Ventilation exhaust fan was functioning as intended at time of
inspection. It is recommended cleaning these units a couple times a year to prevent dirt/lint from affecting the proper
performance of ventilation fans.
|
||||
![]() |
9.1.E | SINK(S) Note:
1. Faucets/spout/drainage were functioning as intended and no observed leakage was present at time of inspection. Monitor in the future. 2. The shut off valves under sinks are not tested. By turning the valves it may cause them to leak also causing damage to the property. Shut off valves are not turned, tested, or operated. |
||||
![]() |
9.2.E | TOILET In Need of Repair: The toilet is loose at the floor and needs to be secured properly to prevent movement and/or possible
leakage which will damage sub flooring under toilet. Conditions under toilet at subfloor are indeterminate . Repair as
required.
Note: A new wax ring should be installed under all loose toilets. As the toilet loosens the seal that is formed from the toilet loosens and the seal is not as tight as it once was. This may result is a leak allowing waste water or sewage gases into the home from a deformed wax ring. |
||||
![]() |
9.3.E | BATHTUB | ||||
![]() |
9.4.E | STALL SHOWER Note: Shower faucets/spouts were observed at time of inspection and elements were functioning as intended. Monitor in
the future.
|
||||
![]() |
9.5.E | BATHROOM LIMITATIONS Note: Only the viewable parts of the vent can be seen during a home inspection. Vent lines can be chased inside of walls
and buried below insulation in the attic. These areas are not viewable during a home inspection.
|
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
SERVICE LINE: Underground |
ENTRANCE LINE: Aluminum 3/0 Aluminum |
SERVICE DISCONNECT(S): Multiple Main Panels Location: In Distribution Panel Garage Estimated: Amps 150 |
MAJOR APPLIANCE (240 VOLT) CIRCUIT(S): Aluminum/Copper |
DISTRIBUTION PANEL: Circuit Breaker Estimated Amps: 150 Location: Garage |
HOUSEHOLD (120 VOLT) CIRCUITS: Copper |
GFCI: At Receptacle(s) |
SPECIAL LIMITATIONS: Appliances Finished Materials |
S | F | P | NA | NI | ||
![]() |
10.0 | SERVICE / ENTRANCE LINE Note: The main conductor lines are underground, or part of a lateral service entrance. This is characteristic of modern
electrical services but, in as much as the service lines are underground and cannot be seen, they are not fully evaluated
as part of our service.
|
||||
![]() |
10.1 | SERVICE GROUNDING PROVISIONS | ||||
![]() |
10.2 | MAIN DISCONNECT(S) | ||||
![]() |
10.3 | DISTRIBUTION PANEL Note: Electrical panels removed for inspection.
Note: Service life of circuit breakers is limited by the erosion of contact material due to arcing that occurs while interrupting the current. If breakers trip frequently, the breaker and the circuit should be evaluated to determine the cause, and corrective action should be taken promptly. The National Electrical code recommends maintenance to the distribution panel every five years consisting of but not limited to re-tightening lugs, proper lubricant on aluminium wiring, etc. Therefore, client should discuss prior maintenance with owner and have serviced by a licensed electrician if of a concern |
||||
![]() |
10.4 | SUBPANEL(S) | ||||
![]() |
10.5 | DEVICES In Need of Evaluation / Correction :
3 prong outlets present at exterior wall in family room and right front bedroom area with open ground.The wiring behind the receptacle may or may not have a ground in the wiring harness. Recommend evaluation/correction by qualified licensed electrician. |
||||
![]() |
10.6 | WIRING Note: No determination was made of individual circuit distribution or accuracy of any circuit labeling. Recommend tracing
and labeling, or confirm correct labeling, of all circuits.
|
||||
![]() |
10.7 | GFCI TEST In Need of Evaluation / Correction :
1.Outlet (s) not GFCI (Ground Fault Circuit Interrupt) protected at all bathrooms with the exception of the bonus room bathroom. When house was built, the requirement was for Bathroom outlets to be GFCI protected. Evaluation/correction by qualified licensed professional electrical contractor recommended. 2.Outlet (s) not GFCI (Ground Fault Circuit Interrupt) protected at Garage and exterior . When house was built, the requirement was for Garage outlets to be GFCI protected. Evaluation/correction by qualified licensed professional electrical contractor recommended. |
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
![]() 10.3 DISTRIBUTION PANEL Item 1(Picture)
|
![]() 10.5 DEVICES Item 1(Picture)
|
![]() 10.7 GFCI TEST Item 1(Picture)
|
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
SYSTEM TYPE: Electric Central Air Conditioning |
SYSTEM MAKE: Lennox Trane Grand Aire |
SYSTEM LOCATION: Condenser Compressor Unit(s) are located at: Right side exterior for Main level Second floor |
ESTIMATED AGE: Over 15 Years 2 to 4 years 8 to 10 years |
DESIGN LIFE: 12 to 15 years |
GENERAL DISTRIBUTION: Ducted/Registers |
S | F | P | NA | NI | ||
![]() |
11.0 | COOLING SYSTEM(S) OPERATION Main Floor :
Temperatures for supply/discharge air were at 52 degrees and return air at 69 degrees with a differential temperature of 17 degrees. Normal operating differentials are between 15-22 degrees. Second Floor : Temperatures for supply/discharge air were at 49 degrees and return air at 70 degrees with a differential temperature of 21 degrees. Normal operating differentials are between 15-22 degrees. Bonus Room : Temperatures for supply/discharge air were at 54 degrees and return air at 70 degrees with a differential temperature of 16 degrees. Normal operating differentials are between 15-22 degrees.
Note: First Floor HVAC , was functional at time of inspection but beyond estimated design life; anticipate replacement needs. It is strongly recommended that a qualified licensed heating and air contractor review your system to help you understand future repairs, remaining life expectancy of system, and replacement budget. |
||||
![]() |
11.1 | OUTDOOR UNIT(S) Note: It is recommended to service and clean unit/system on an annual basis to assist in system functioning properly and
maximize energy efficiency. Also, keep a three foot clearance around the perimeter of the unit to prevent restriction of air
flow and hence, higher energy consumption.
|
||||
![]() |
11.2 | INDOOR BLOWER / FAN In Need of Repair :
Insulation is not extended on suction line to coil cabinet in bonus room area , this is a conducive condition for water to drip on attic floor/drain pan , repair as required |
||||
![]() |
11.3 | CONDENSATE PROVISIONS Note: It is recommended that the condensation line is maintained and kept clear of any foreign debris, etc. to allow drain
line to function as intended to prevent condensation to back up into unit/system which can affect system and its
components. Also, it is recommended to monitor the condensate line termination point for water flow during cooling
season. Your cooling system can produce gallons of water a day and can overflow if restricted.
|
||||
![]() |
11.4 | DISTRIBUTION SYSTEM Note: Distribution irregularities can be due to system design or installation deficiencies (e.g., balancing, limited supply registers, etc.). A thorough evaluation by a qualified HVAC specialist will be required to determine corrective action required. Generally, house heating will be affected by heat stratification and house or system design factors. |
||||
![]() |
11.5 | THERMOSTAT Note: Consult with the owner on operation, and confirm proper operation of system. Inspection of any thermostat
condition is limited to its physical condition, mounting methods, and basic response to set point adjustment for cooling
system operation. No evaluation is made of calibration accuracy, response time, effectiveness, or the function of each and
every feature or components.
|
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
![]() 11.0 COOLING SYSTEM(S) OPERATION Item 1(Picture)
| |
![]() 11.0 COOLING SYSTEM(S) OPERATION Item 2(Picture)
|
![]() 11.0 COOLING SYSTEM(S) OPERATION Item 3(Picture)
|
![]() 11.0 COOLING SYSTEM(S) OPERATION Item 4(Picture)
|
![]() 11.0 COOLING SYSTEM(S) OPERATION Item 5(Picture)
|
![]() 11.0 COOLING SYSTEM(S) OPERATION Item 6(Picture)
|
![]() 11.2 INDOOR BLOWER / FAN Item 1(Picture)
|
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
SYSTEM: MAKE: Comfortmaker Lennox |
SYSTEM TYPE: Hot Air-Fuel: Gas-Furnace Fuel: Natural Gas |
SYSTEM LOCATION: Crawlspace for First Floor Interior closet |
ESTIMATED AGE: 2 to 4 years Over 20 years |
DESIGN LIFE: 15 to 20 years |
GENERAL DISTRIBUTION: Ducted/Registers |
S | F | P | NA | NI | ||
![]() |
12.0 | HEATING SYSTEM(S) OPERATION Note: Evaluations are usually restricted to the basic operation of Gas furnaces. No heat gain, sizing, or design
evaluations were performed. Thermostat calibration, accuracy and adequacy of conditioned air distribution were not
determined. The heat exchanger and internal components are not visible for inspection. Rated fair due to age and
functions as intended. Client may consider having system/unit(s) evaluated/repaired by qualified licensed professional
HVAC contractor before closing to ensure proper function of system (s) which is beyond the normal scope of a home
inspection.
Note: Functional at time of inspection for bonus room but beyond estimated design life; anticipate replacement needs. It is strongly recommended that a qualified licensed heating and air contractor review your system to help you understand future repairs, remaining life expectancy of system, and replacement budget. |
||||
![]() |
12.1 | BURNERS Note: Heat exchangers/burner compartments are not inspected except thru available grille. System has to be dismantled
for this type of inspection and is technically exhaustive and not part of the home inspection. Some systems do not have
available access to visually see thru grille to view burner compartment. Therefore, it is highly recommended that a review
of the heat exchanger/system by qualified licensed Heating contractor be performed prior to closing.
|
||||
![]() |
12.2 | GAS / FUEL LINES AT UNIT | ||||
![]() |
12.3 | VENT CONNECTOR In Need of Evaluation / Correction :
B Vent flue in attic kneewall area at left side is damaged and a safety concern as it can leak carbon monoxide into the living area , recommend evaluation /correction by a licensed HVAC contractor . Note : It could not be determined if this flue pipe is still being utilized . |
||||
![]() |
12.4 | BLOWER | ||||
![]() |
12.5 | DISTRIBUTION SYSTEM | ||||
![]() |
12.6 | THERMOSTAT | ||||
![]() |
12.7 | HEATING SYSTEM LIMITATIONS Heat exchangers/burner compartments are not inspected except thru available grille. System has to be dismantled for
this type of inspection and is technically exhaustive. Some systems do not have available access to visually see thru grille
to view burner compartment. Consider review of heat exchanger/system by licensed Heating contractor as desired
before closing.
|
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
![]() 12.3 VENT CONNECTOR Item 1(Picture)
|
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
WATER PIPING: Copper |
WATER SHUT-OFF LOCATION: Not Determined |
GAS SHUT-OFF LOCATION: At Meter |
DRAIN/WASTE/VENT LINES: ABS |
WATER TREATMENT SYSTEM: Not Applicable |
SPECIAL LIMITATIONS: Personnel Belongings Insulation Finished Areas |
S | F | P | NA | NI | ||
![]() |
13.0 | MAIN WATER CUTOFF Note: A shut-off for the water-supply system could not be located at/in the house as it may have been blocked or covered
by stored items. Check with the current owners for the location, prior to closing. It is important to identify the location of
the main water shut off valve in the event of and emergency. If not present, then acquire and use a water key at the street
or have a plumber install a valve.
|
||||
![]() |
13.1 | WATER PIPING Note: Neither the source, type nor quality of water supply, nor the method of waste disposal is determined as part of a
standard home inspection. Advise obtaining documentation/verification of type systems. If a private water and/or waste
system exists, independent evaluation by a specialist is recommended. Evaluation of the plumbing system was limited to
permanently connected fixtures and readily visible pipe conditions. The function and effectiveness of laundry standpipes,
vent pipes, floor drains, fixture overflows, anti-siphon devices and similar items generally cannot be evaluated. Conditions
are subject to unpredictable change, e.g., leaks may develop, water flow may drop, drains may become blocked, etc.
The detection of sewer gases and the condition/function of sub-slab or in-ground piping is excluded from a standard
inspection. In-ground piping is subject to blockage/collapse.
|
||||
![]() |
13.2 | WATER FLOW AT FIXTURES Note: Many modern faucets and fixtures have flow restrictors that limit the amount of water that can pass through the
faucet in a given amount of time. These restrictors often have tiny holes that limit the amount of water flow. Due to small
pieces of sediment or some other debris that clogged a passageway within the valve cartridge and/or the tiny orifices
within the aerator and or a flow restrictor you will have reduced water flow. The sediment can form within a faucet or its
parts depending upon the hardness of your water. Sediment also forms as a scale on the inside of municipal water supply
pipes and the water lines inside your home. Pieces of this sediment can break off and be transported through the water
lines as water moves towards a faucet. Small pieces of sand or rocks can enter a water system, especially those of
people who use a private well.
|
||||
![]() |
13.3 | DRAIN / WASTE / VENT PIPING Note: Main drain line for home to either a septic system or municipal system is not part of a home inspection and is not
evaluated. We attempt to evaluate drain pipes by flushing every drain that has an active fixture while observing its draw
and watching for blockages or slow drains, but this is not a conclusive test and only a video-scan of the main line would
confirm its actual condition. However, you can be sure that blockages will occur, usually relative in severity to the age of
the system, and will range from minor ones in the branch lines, or at the traps beneath sinks, tubs, and showers, to major
blockages in the main line. The minor ones are easily cleared, either by chemical means or by removing and cleaning the
traps. However, if tree roots grow into the main drain that connects the house to the public sewer, repairs could become
expensive and might include replacing the entire main line. For these reasons, we recommend that you ask the sellers if
they have ever experienced any drainage problems, or you may wish to have the main waste line video-scanned prior to
closing by a qualified licensed plumber.
|
||||
![]() |
13.4 | FIXTURE DRAINAGE Note: A sluggish or blocked drain in the future may indicate a localized concern or may be related to the condition or flow
of branch or main waste lines. You may want to have checked by a qualified licensed plumber to determine whether
cleaning or other corrective measures are required.
|
||||
![]() |
13.5 | EXTERIOR FAUCET(S) | ||||
![]() |
13.6 | GAS PIPING | ||||
![]() |
13.7 | PLUMBING SYSTEM LIMITATIONS The plumbing supply, drains, waste and vent piping materials were only visible in the crawlspace, attic area and at
interior fixture locations.
|
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
MANUFACTURER: American Bradford White |
WATER HEATER LOCATION: Garage Interior closet |
WATER HEATER TYPE: Direct-heated Tank Fuel: Natural Gas Fuel: Electric |
DESIGN LIFE: 8 to 12 years |
ESTIMATED CAPACITY: 40 Gallons 50 Gallons |
ESTIMATED AGE: 4 to 6 years 10 to 12 years |
S | F | P | NA | NI | ||
![]() |
14.0 | WATER HEATER Note:
1. Although, functional at time of inspection, anticipate repairs/servicing. Water heaters should be flushed every year or as recommended by the manufacturer to remove sediments that collects at the bottom of the tank. 2. Recovery rate (length of time unit produces hot water) not determined within the scope of a standard inspection and typically shortens as age increases. Replacement may be required if recovery time is reduced to less than clients expectations. The capacity of the water heater was described however it is not possible to determine if the capacity of this system will be adequate for the demands placed on it by a family |
||||
![]() |
14.1 | VENT CONNECTOR | ||||
![]() |
14.2 | GAS / FUEL LINES AT UNIT | ||||
![]() |
14.3 | SAFETY VALVE PROVISIONS In Need of Repair: The drain tube for the TPRV Valve should be terminated to a visible location at the exterior for the
water heater in the garage.
|
||||
![]() |
14.4 | THERMAL EXPANSION TANK In Need of Evaluation / Correction :
A thermal expansion tank is a pressurized tank that sits on your cold water line at or near the water heater. The tank contains a pressurized bladder that expands as water presses against it, giving that water a place to go and reducing the pressure on the rest of your water heater as the volume increases. Missing thermal expansion tank for plumbing system required for water heaters installed after 2012. Evaluation/correction by qualified licensed plumbing contractor recommended. Note : Applies to electric water heater in garage. |
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
![]() 14.3 SAFETY VALVE PROVISIONS Item 1(Picture)
|
![]() 14.4 THERMAL EXPANSION TANK Item 1(Picture)
|
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
BASEMENT: Not Applicable |
CRAWLSPACE: Full House |
CRAWLSPACE ACCESS LOCATION: Right Side of Home |
CRAWLSPACE INSPECTION METHOD: Entered |
FOUNDATION WALLS/PIERS: CMU(block)/brick |
HOUSE FLOOR STRUCTURE: Joist |
INSULATION: Blankett/Batt - Fiberglass |
SPECIAL LIMITATIONS: Insulation Inaccessible areas at: Left Side Rear |
TOOLS USED FOR CRAWLSPACE INSPECTION: Flashlight Camera Moisture Meter Screw Driver/Probe |
S | F | P | NA | NI | ||
![]() |
15.0 | FOUNDATION WALLS | ||||
![]() |
15.1 | PIERS / COLUMNS | ||||
![]() |
15.2 | FLOOR FRAMING Refer to MAIN BEAMS
|
||||
![]() |
15.3 | MAIN BEAM(S) In Need of Evaluation / Correction :
Evidence of moisture damaged beams at various areas especially at rear areas,along with damage noted from wood destroying insects observed at same areas as above . In addition " helper supports" were observed at rear area and are not functioning for what they are intended for . Recommend evaluation /correction by a licensed qualified contractor for all framing members and their components . Note : A representative amount of framing members were probed at time of inspection ,due to high moisture concerns , various sub structure framing members were observed to have possible fungi/mold which can weaken the structural members, after moisture issues are resolved there could be implied damage as the framing members dry , it is recommended to have the substructure inspected by a licensed qualified contractor after the moisture concern is resolved , Housemaster will not be responsible for any substructure framing concerns due to these prior conditions . Note : Previous repairs observed to framing members. Note : Pictures shown are examples only , not all areas of concern have pictures . |
||||
![]() |
15.4 | INSULATION | ||||
![]() |
15.5 | FOUNDATION / SUB-STRUCTURE LIMITATIONS Note: The under the floor insulation, between the floor joists restricts viewing of the subfloor area and a percentage of the
floor joists.
Note: Limited access to crawl space at rear left due to lack of clearance , this is a limitation to inspection. |
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
![]() 15.3 MAIN BEAM(S) Item 1(Picture)
|
![]() 15.3 MAIN BEAM(S) Item 2(Picture)
|
![]() 15.3 MAIN BEAM(S) Item 3(Picture)
|
![]() 15.3 MAIN BEAM(S) Item 4(Picture)
|
![]() 15.3 MAIN BEAM(S) Item 5(Picture)
|
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() Report ID: 1806SM2010 / Report |
DESCRIPTION: Crawl Space Area(s) |
INDICATIONS OF PRIOR REMEDIAL WORK: Construction/repairs |
SPECIAL LIMITATIONS: Moisture barrier Insulation |
SUMP PUMP(S): Submersible |
S | F | P | NA | NI | ||
![]() |
16.0 | CRAWLSPACE In Need of Evaluation / Correction :
1.Appears to have ongoing water penetration concern at rear areas Wet soil at areas of crawlspace . Evidence of possible prior standing water/high water marks present on foundation walls. Due to concerns observed: Evaluation/correction by qualified contractor recommended. 2.The average moisture content of framing members throughout the crawlspace was between 21-27 %. This is at or above the 20% threshold where rot/decay typically begins and is a conducive condition for wood destroying insects.. When building components have surface discolorations and decay typical of fungal growths, such as mold,mildew, and wood destroying fungi , the home inspection focuses only on moisture concerns and evidence of wood damage . Health issues related to the presence of mold are beyond the scope of the home inspection . If the client has concerns beyond the scope of the home inspection , a certified professional such as an industrial hygienist should be consulted prior to purchasing the home . |
||||
![]() |
16.1 | SUMP PUMP(S) Note: Sump pump could not be operated/inspected for function due to no water in sump pit. and electrical outlet .
|
||||
![]() |
16.2 | FOUNDATION AREA WATER PENETRATION LIMITATIONS Note: Limited access to crawl space at rear left due to lack of clearance , this is a limitation to inspection.
|
||||
S | F | P | NA | NI | S= Satisfactory, F= Fair, P= Poor/Defective, NA= Not Applicable, NI= Not Inspected |
![]() 16.0 CRAWLSPACE Item 1(Picture)
| |
![]() 16.0 CRAWLSPACE Item 2(Picture)
| |
![]() 16.0 CRAWLSPACE Item 3(Picture)
|
![]() 16.0 CRAWLSPACE Item 4(Picture)
|
![]() 16.0 CRAWLSPACE Item 5(Picture)
|
(c) Copyright 2001 - 2025 HouseMaster | Each HouseMaster Franchise is an Independently Owned and Operated Business. |
![]() |
![]() |
Report ID: 1806SM2010 / Report |
INSPECTION CERTIFICATION | ||||||||
The undersigned hereby certifies that this inspection was conducted pursuant to accepted Home Inspection Standards of Practice . Furthermore, neither the undersigned nor the inspection company has any interest, present or contemplated, in this property and neither the retention of the inspection company nor compensation paid is contingent on report findings. | ||||||||
|
||||||||
Stuart Malamut, Inspector | ||||||||
SC License # RBI-48724 | ||||||||
Inspection Date: 6/7/2018 | ||||||||
|
||||||||